Lose
Loop Fumigation.
Phosphine fumigation can be improved by using a
closed loop fumigation (CLF) system. A correctly installed CLF system
will use less fumigant, save on labor costs after the initial installation,
cause less worker exposure which will lead to less health costs, and improve
insect control. In a test at a concrete facility that was divided into
two sections where one side received conventional treatment and the other side
had a CLF system, phosphine levels reached over 2,000 ppm on the CLF side and
only a maximum of 100 ppm on the conventionally treated side. Sealing and
using a CLF system will save you money and result in better control of insect
pests.
Closed-loop
Fumigation Systems
A closed-loop fumigation (CLF)
system can be added to many grain storage structures to speed up the
distribution of phosphine gas and make the concentration more uniform
throughout. A drawing of a CLF system on a round grain bin is shown in Figure
1. For a typical closed-loop fumigation, aluminum or magnesium phosphide
pellets or tablets are placed on top of the grain where they react with
moisture
in the air to produce phosphine
gas (PH3). The CLF system uses a small fan to recirculate air/PH3 in the bin by
drawing it out of the headspace and introducing it back into the bottom of the
bin. There the fumigant passes through the perforated floor and into the grain
mass. The fumigant passes upward through the grain until it enters the
headspace where the cycle repeats. The CLF system is operated after the
tablets/pellets are completely reacted. After several cycles through the bin,
the fumigant is evenly distributed. Following the initial redistribution of
air/PH3 the CLF fan is operated only when periodic monitoring shows the
concentration of PH3 has become uneven.
At the end of fumigation, residual phosphine must be removed from
the bin. If the bin is not equipped with an aeration fan, the CLF fan can be
used to purge phosphine by disconnecting the fan intake duct and introducing
fresh air into the bin. This will push fumigant out through roof vents and
eventually the PH3 concentration will drop to safe levels.
Design
of CLF Systems
Every grain storage facility is
different and a designer must take many factors into consideration when designing
a CLF system for a grain storage facility. The sections that follow suggest
steps in the design of a CLF system and present example calculations and
photographs.
Airflow Rate
When designing a CLF system for a grain storage facility, the
first step is to determine the appropriate flow rate of air/fumigant through
the structure. The flow rate of the CLF system should provide several air
exchanges per day in the bin to ensure good mixing. The CLF flow rate can be
calculated by dividing the volume of air in the grain bin by the desired air
exchange time. The volume of air in the bin includes the air in between the
grain kernels plus the air in the headspace above the grain and in any aeration
plenums. If a bin is only partially filled or has a large headspace, as in the
case of some flat storage facilities, the air exchange times will be longer for
a given flow rate because the grain is not displacing air in the bin. For many
bins, the headspace and plenum volume are small compared to the grain volume
and can be ignored. In this case, recommended CLF airflow rates should be
between 0.002 and 0.010 CFM/bushel of grain. These airflow rates result in air
exchange times ranging between 4.2 and 0.8 hours respectively, as shown in
Figure 2. These airflow rates are much less than recommended for aeration
cooling of grain. Low airflow rates reduce pressure differentials across the
grain, thus reducing leakage. Lower airflow rates also reduce capital and
energy costs for the CLF system.
Airflow Path
After the airflow rate is determined,
the next step is to determine the fumigant circulation path through the
structure. The direction of air flow is generally not important although flow
from bottom to top through the grain is most common. For bins with an aeration
plenum or ducts at the bottom, as shown in Figure 1, the fumigant circulation
path is fairly straight forward because it usually makes sense to use existing
equipment. In flat storage facilities or concrete silos without aeration, the
design of the airflow path can be more challenging. The injection point(s) into
the grain mass should be located geometrically opposite the gas exit point(s).
A sufficient amount of perforated area is needed to allow the fumigant to
freely exit the duct and enter the grain mass. The holes should be as large as
possible, but not so large that grain falls through. For minimum pressure loss
the total open area of the perforations should be one square foot per 300 CFM
of airflow. If less open area is provided, an engineer should calculate the
static pressure developed across the perforated duct.
In a concrete elevator the air/PH3 injection point can be through
a manhole cover (Figure 3) or unloading spout (Figure 4) near the bin bottom.
The fumigant can exit the silo at the top through either a manhole cover
(Figure 5) or a vent fitted to accept the suction hose from the CLF fan. A
concrete elevator typically has multiple grain bins. A single CLF fan can be
connected to a distribution manifold (Figure 6 and Figure 7) that connects
multiple bins. Individual bins can be isolated from, or connected to, the
fumigation by opening and closing ball valves (Figures 3 and 4) at the entry
and exit to each individual bin. These valves can also be used for pressure
testing the ducts to detect leaks before fumigation. The CLF duct(s) from the
top of the elevator to the bottom can either be routed through service shafts
internal to the structure or on the outside.
For flat storage, injection of air/PH3 can be through perforated
ducts buried at the bottom of the grain. The fumigant exits these ducts and
then moves up through the grain into the headspace of the structure to be
recaptured and recirculated by the CLF fan. Multiple injection locations are
required for large flat storage structures to decrease the time required to
evenly distribute phosphine. Spacing between injection points should be no more
than the depth of the grain. Distance from the sidewalls to the nearest
injection point should not exceed one half the grain depth
CLF duct selection and
routing
Permanently mounted CLF ducts can be
made from PVC pipe anchored to the structure’s walls with commercially available
pipe hangers (Figure 6). A wide variety of fittings, valves and attachment
hardware are readily available for schedule 40 PVC pipe for routing ducts
around obstructions and making distribution manifolds (Figure 7). Black
plastic corrugated drain hose in 3-inch, 4-inch, and 6-inch diameters can be
used where temporary flexible connections are required (Figure 5). For smaller
diameter flexible connections, reinforced hoses can be used (Figures 3 and 4).
Exposure to ultraviolet light from the sun can degrade PVC and other plastic
duct materials over time. If this is a concern, the duct can be covered or
painted per the manufacturer’s recommendations.
If the fan and other electrical components are located inside the
bin or head house they must conform to explosion-proof design criteria.
Mounting them outside in open air away from explosion hazards (Figure 5) can
save on installation costs, but this may make duct routing more difficult and
require shielding from the weather.
If the CLF system will be used to purge the bin at the end of
fumigation, provisions in the duct system should be made to vent residual PH3
in a safe area. Furthermore personnel should not have to enter hazardous areas
to operate valves or other controls when purging bins.
Ducts should be sized to minimize cost of the entire CLF system.
Smaller ducts have lower material costs and requireless labor to install.
However smaller ducts result in higher air velocities to get the desired
airflow rate. Increased velocity increases resistance to airflow which in turn
increases the power and cost of the fan.
No comments:
Post a Comment