General Agriculture

"Empowering farmers with knowledge and utilizing available resources can revolutionize agricultural productivity. From leveraging modern technology to optimizing traditional methods, there's a wealth of strategies at our fingertips. Let's cultivate awareness among farmers, ensuring they harness every tool and technique for a bountiful harvest

Friday 22 April 2016

Store grain pests control, Lose Loop Fumigation.

Lose Loop Fumigation.

Phosphine fumigation can be improved by using a closed loop fumigation (CLF) system.  A correctly installed CLF system will use less fumigant, save on labor costs after the initial installation, cause less worker exposure which will lead to less health costs, and improve insect control.  In a test at a concrete facility that was divided into two sections where one side received conventional treatment and the other side had a CLF system, phosphine levels reached over 2,000 ppm on the CLF side and only a maximum of 100 ppm on the conventionally treated side.  Sealing and using a CLF system will save you money and result in better control of insect pests.

 Closed-loop Fumigation Systems
A closed-loop fumigation (CLF) system can be added to many grain storage structures to speed up the distribution of phosphine gas and make the concentration more uniform throughout. A drawing of a CLF system on a round grain bin is shown in Figure 1. For a typical closed-loop fumigation, aluminum or magnesium phosphide pellets or tablets are placed on top of the grain where they react with moisture
in the air to produce phosphine gas (PH3). The CLF system uses a small fan to recirculate air/PH3 in the bin by drawing it out of the headspace and introducing it back into the bottom of the bin. There the fumigant passes through the perforated floor and into the grain mass. The fumigant passes upward through the grain until it enters the headspace where the cycle repeats. The CLF system is operated after the tablets/pellets are completely reacted. After several cycles through the bin, the fumigant is evenly distributed. Following the initial redistribution of air/PH3 the CLF fan is operated only when periodic monitoring shows the concentration of PH3 has be­come uneven.
At the end of fumigation, residual phosphine must be removed from the bin. If the bin is not equipped with an aeration fan, the CLF fan can be used to purge phosphine by disconnecting the fan intake duct and introducing fresh air into the bin. This will push fumigant out through roof vents and eventually the PH3 concentration will drop to safe levels.
Design of CLF Systems
Every grain storage facility is different and a designer must take many factors into consideration when designing a CLF system for a grain storage facility. The sections that fol­low suggest steps in the design of a CLF system and present example calculations and photographs.
Airflow Rate
When designing a CLF system for a grain storage facil­ity, the first step is to determine the appropriate flow rate of air/fumigant through the structure. The flow rate of the CLF system should provide several air exchanges per day in the bin to ensure good mixing. The CLF flow rate can be calculated by dividing the volume of air in the grain bin by the desired air exchange time. The volume of air in the bin includes the air in between the grain kernels plus the air in the headspace above the grain and in any aeration plenums. If a bin is only partially filled or has a large headspace, as in the case of some flat storage facilities, the air exchange times will be longer for a given flow rate because the grain is not displacing air in the bin. For many bins, the headspace and plenum volume are small compared to the grain volume and can be ignored. In this case, recommended CLF airflow rates should be between 0.002 and 0.010 CFM/bushel of grain. These airflow rates result in air exchange times ranging between 4.2 and 0.8 hours respectively, as shown in Figure 2. These airflow rates are much less than recommended for aeration cooling of grain. Low airflow rates reduce pressure differentials across the grain, thus reducing leakage. Lower airflow rates also reduce capital and energy costs for the CLF system.
Airflow Path
After the airflow rate is determined, the next step is to determine the fumigant circulation path through the structure. The direction of air flow is generally not important although flow from bottom to top through the grain is most common. For bins with an aeration plenum or ducts at the bottom, as shown in Figure 1, the fumigant circulation path is fairly straight forward because it usually makes sense to use existing equipment. In flat storage facilities or concrete silos without aeration, the design of the airflow path can be more challenging. The injection point(s) into the grain mass should be located geo­metrically opposite the gas exit point(s). A sufficient amount of perforated area is needed to allow the fumigant to freely exit the duct and enter the grain mass. The holes should be as large as possible, but not so large that grain falls through. For minimum pressure loss the total open area of the perfo­rations should be one square foot per 300 CFM of airflow. If less open area is provided, an engineer should calculate the static pressure developed across the perforated duct.
In a concrete elevator the air/PH3 injection point can be through a manhole cover (Figure 3) or unloading spout (Figure 4) near the bin bottom. The fumigant can exit the silo at the top through either a manhole cover (Figure 5) or a vent fitted to accept the suction hose from the CLF fan. A concrete el­evator typically has multiple grain bins. A single CLF fan can be connected to a distribution manifold (Figure 6 and Figure 7) that connects multiple bins. Individual bins can be isolated from, or connected to, the fumigation by opening and closing ball valves (Figures 3 and 4) at the entry and exit to each individual bin. These valves can also be used for pressure testing the ducts to detect leaks before fumigation. The CLF duct(s) from the top of the elevator to the bottom can either be routed through service shafts internal to the structure or on the outside.
For flat storage, injection of air/PH3 can be through per­forated ducts buried at the bottom of the grain. The fumigant exits these ducts and then moves up through the grain into the headspace of the structure to be recaptured and recirculated by the CLF fan. Multiple injection locations are required for large flat storage structures to decrease the time required to evenly distribute phosphine. Spacing between injection points should be no more than the depth of the grain. Distance from the sidewalls to the nearest injection point should not exceed one half the grain depth
CLF duct selection and routing
Permanently mounted CLF ducts can be made from PVC pipe anchored to the structure’s walls with commercially avail­able pipe hangers (Figure 6). A wide variety of fittings, valves and attachment hardware are readily available for schedule 40 PVC pipe for routing ducts around obstructions and mak­ing distribution manifolds (Figure 7). Black plastic corrugated drain hose in 3-inch, 4-inch, and 6-inch diameters can be used where temporary flexible connections are required (Figure 5). For smaller diameter flexible connections, reinforced hoses can be used (Figures 3 and 4). Exposure to ultraviolet light from the sun can degrade PVC and other plastic duct materi­als over time. If this is a concern, the duct can be covered or painted per the manufacturer’s recommendations.
If the fan and other electrical components are located inside the bin or head house they must conform to explosion-proof design criteria. Mounting them outside in open air away from explosion hazards (Figure 5) can save on installation costs, but this may make duct routing more difficult and require shielding from the weather.
If the CLF system will be used to purge the bin at the end of fumigation, provisions in the duct system should be made to vent residual PH3 in a safe area. Furthermore personnel should not have to enter hazardous areas to operate valves or other controls when purging bins.
Ducts should be sized to minimize cost of the entire CLF system. Smaller ducts have lower material costs and requireless labor to install. However smaller ducts result in higher air velocities to get the desired airflow rate. Increased velocity increases resistance to airflow which in turn increases the power and cost of the fan.

No comments:

Post a Comment

Social Widget

Followers

$(".comments .avatar-image-container img").attr("src", function($this, img) { if (img.match("hqdefault.jpg")) { return img.replace("/hqdefault.jpg", "/mqdefault.jpg"); } else if (img.match("default.jpg")) { return img.replace("/default.jpg", "/mqdefault.jpg"); } else if (img.match("s35-c")) { return img.replace("/s35-c", "/s100-c"); } else if (img.match("s72-c")) { return img.replace("/s72-c", "/s100-c"); } else if (img.match("w72-h72-p-nu")) { return img.replace("/w72-h72-p-nu", "/s100-c"); } else { return img.replace("http://3.bp.blogspot.com/-Yw8BIuvwoSQ/VsjkCIMoltI/AAAAAAAAC4c/s55PW6xEKn0/s1600-r/nth.png"); } }); //]]>